China Nissan Oil Filter,Oil Filter For Nissan,Nissan Car Oil Filter,Nissan Auto Oil Filter, we offered that you can trust. Welcome to do business with us. Nissan Oil Filter,Oil Filter For Nissan,Nissan Car Oil Filter,Nissan Auto Oil Filter Zhoushan Shenying Filter Manufacture Co., Ltd. , https://www.renkenfilter.com
1. The default IP address of the LAN port of the HINET smart gateway is 192.168.1.1;
2. Assuming that the IP address of the PLC is 192.168.10.2, and the requirement cannot be changed;
3. Change the IP address of the LAN port of the HINET smart gateway to 192.168.10.X to ensure normal communication with the PLC (assuming it is changed to 192.168.10.254);
3.1 Connect the LAN port of the HINET smart gateway to the computer;
3.2 Add the 192.168.1.X gateway IP to the computer, if there is no need to add it;
3.3 Open the IE browser and enter the IP address of the HINET smart gateway LAN port 192.168.1.1;
3.4 Enter the user name and password, the default is admin;
3.5 Click "network", and enter the network configuration page; (the language selection under the System option can be converted to a Chinese page)
3.6 Select "Edit" after the LAN port to enter the modification page;
3.7 Modify the IP to 192.168.10.254 and click "Save&Apply". (No other configuration needs to be changed)
4 Open the PLC programming software, click "controller programming settings", select "Internet" programming communication method and enter the IP address 192.168.10.2;
5 Hardware connection, HINET smart gateway LAN port is connected to PLC, WAN port is connected to the Internet;
6 Add the AC 500 PLC device on the HINET cloud server;
6.1 Enter the HINET cloud server address in the IE browser: plc.hignton.com/v2, and enter the correct corporate account and password (by default, the corporate name is the full name of the client's company, and the password is 12345678);
6.2 Click "Device Management" to enter the device management page, where the device refers to PLC and other devices;
6.3 Click "Add" to add PLC equipment according to the specified format;
6.4 Click OK and enable, the device is added.
7 Install the HINET smart gateway client and enter the correct user name and password (the user name and password can be added and modified in the HINET cloud service by the customer);
8 Enter the home page of the client and you can see the AC 500PLC just created;
9 Double-click to select the PLC to enter the remote connection page, click "join network group" and "build connection channel";
10 When all the four indicators light up, it means that the PLC has been successfully connected remotely.
11 Minimize the client software (do not close it), open the AC500 programming tool or configuration, and follow the programming method of the PLC local connection to remotely program the PLC, upload and download and configure remotely, and read various data.
Haide PLC remote programming and debugging process
Remote programming
Remote configuration screen